The popular UK heat pump lines, compared on published specs

Every manufacturer claims efficiency. The useful comparison is the published numbers side by side, with the measurement conditions attached, because a SCOP quoted at 35C flow and one quoted at 65C flow are not the same claim.

Updated 25 September 2026 · written by the Clearline guidance team · 6 min read

11 dated sources, listed in full below Plain English, written to explain before anyone quotes Figures recomputed at every update, never recycled
An air source heat pump outdoor unit mounted at a UK terraced house

How to read any heat pump spec sheet

Before the table, three rules. A SCOP figure is meaningless without the flow temperature it was measured at, because efficiency falls sharply as flow temperature rises. A noise figure is meaningless without knowing whether it is sound power or sound pressure, and if it is pressure, at what distance. And an output figure is meaningless without the air temperature it was rated at, because capacity falls as it gets colder outside.

Every number below carries its condition where the manufacturer publishes one. Where a figure comes from a review rather than a datasheet, it says so.

The badge matters less than the design

The Electrification of Heat trial monitored 742 heat pumps and found high variation in performance between installations, with a median in situ SPF of 2.80 across air source systems. That spread is wider than the spread between the units below. Choosing well matters. Designing well matters more.

The published specifications

LineOutputsRefrigerantMax flow tempPublished efficiency
Vaillant aroTHERM plus
3.5, 5, 7, 10, 12 kW
R290, GWP of 3
75C
SCOP up to 5.03
Mitsubishi Electric Ecodan R290
5 to 16 kW
R290
75C
SCOP 3.5 to 4.2 by size (review sourced)
Daikin Altherma 3 R
Standard monobloc range
R32 Bluevolution
Standard temperature
A+++ seasonal efficiency label
Daikin Altherma 3 H HT
Approx 11 to 13 kW, three classes
High temperature line
70C
SCOP 4.71 at 35C
Samsung EHS Mono R290 Gen 7
5, 8, 12, 16 kW
R290
Standard temperature
SCOP up to 4.84 at 35C on the 5 kW
Samsung EHS Mono HT Quiet
8, 12, 14 kW
R32
Hot water to 70C
SCOP 2.82, 3.01, 3.03 at 65C flow
Grant Aerona 290
4, 6.5, 9, 12, 15.5 kW single phase
R290
Rated at 55C water flow
A+++ energy label
Ideal Logic Air
4 to 10 kW
R32
Standard temperature
SCOP 5.16 to 5.19 at 35C, 3.7 to 3.73 at 55C (review sourced)
Worcester Bosch Compress 7001i AW
5, 7, 9, 13 kW
Manufacturer data sheet
Manufacturer data sheet
Manufacturer data sheet
Octopus Cosy 6
See note
R290
Own-brand monobloc
Real world SCOP up to 4.12 claimed (review sourced)

Grant Aerona 290 outputs are each rated at minus 5C air temperature and 55C water flow, which is a colder and more demanding basis than many nominal figures. Octopus Cosy 6 nominal output figures vary between sources, so we do not publish a kW claim for it here: check the current Octopus datasheet. Blank cells mean the manufacturer publishes the figure but we have not verified it directly.

An air source heat pump outdoor unit mounted at a UK terraced house
An air source heat pump outdoor unit. Siting drives both performance and planning.

The R290 shift, and why it matters to you

The clearest market pattern in 2026 is refrigerant. Vaillant, Mitsubishi Electric, Samsung, Grant and Octopus all now lead with R290, which is propane, quoted by Vaillant at a global warming potential of 3. Daikin's mainstream Altherma 3 R uses R32, and Samsung keeps R32 on its high temperature Mono HT Quiet line.

How a heat pump moves heat into your home Four steps that follow the heat. One, outside air holds usable heat even when the weather is cold. Two, the refrigerant absorbs that heat and the compressor raises its temperature. Three, the heat transfers across into your water circuit. Four, radiators or underfloor pipes release it into the room. How a heat pump moves heat 1 Outside air Holds usable heat even on a cold day 2 Refrigerant and compressor It takes the heat in, then lifts the temperature 3 Your water circuit The heat passes into your heating water 4 Radiators or underfloor Warmth is released into the room
The refrigerant is what carries heat through the compressor stage of the cycle.

The homeowner consequence is temperature. R290 units reach 70 to 75C flow, which is what makes keeping most of your existing radiators viable and what lets the heat pump handle cylinder hot water without leaning on an immersion heater. Vaillant states directly that the aroTHERM plus reaching 75C allows cylinder hot water without an immersion top up for legionella protection. That is a real running cost difference, not a marketing point.

High temperature capability is not a licence to run hot

A unit that reaches 75C should still be designed to the lowest flow temperature your emitters allow. Samsung's own numbers show the penalty: SCOP up to 4.84 at 35C flow against 2.82 to 3.03 at 65C. Buy the capability as a safety net, then design so you rarely use it.

Get my free quote

Three details. We call or text within one working day to book your free 30-minute design call, on video or by phone if you prefer.

Please add your full postcode
Please add your first name
Please enter a UK mobile or landline

Free, no obligation, nobody visits your home. Prefer to talk? 07782 219224

Your design call is with Niall or Vince, our residential energy consultants.

Cold weather operation

Three of the lines publish an operating floor well below anything the British climate produces. Vaillant quotes the aroTHERM plus as operating down to minus 25C. The Mitsubishi Electric Ecodan R290 datasheet quotes the same minus 25C. Daikin quotes operation down to minus 25C on the Altherma 3 R.

Grant takes a different and arguably more honest approach with the Aerona 290, rating each output at minus 5C air temperature and 55C water flow rather than at a flattering mild condition. When you compare kW figures across brands, check what condition each one was measured at before concluding one unit is bigger than another.

Wondering which of these would actually suit your property and your radiators? The free remote design call answers that without a sales pitch.

Get my free quote →

Noise, and why the figures do not compare directly

Manufacturers publish either sound power, which is the total acoustic energy the unit emits, or sound pressure, which is what you would measure at a stated distance. They are different measurements and comparing one against the other tells you nothing.

  • Vaillant claims sound pressure below 30 dB(A) at 3 metres for the aroTHERM plus.
  • Daikin quotes the Altherma 3 H HT at 38 dB(A) sound pressure at 3 metres in standard mode, and 35 dB(A) in low sound mode.
  • Samsung quotes a 35 dB(A) quiet mode on the EHS Mono R290, and a four step quiet mode down to 35 dB(A) on the Mono HT Quiet.
  • Mitsubishi Electric standard Ecodan models are reported at around 55 dB(A) sound power, with Ultra Quiet PUZ variants at 45 to 48 dB, both review sourced rather than taken from a manufacturer datasheet.

What actually governs whether a unit can go where you want it is not the datasheet, it is the MCS 020 (a) sound calculation, which must show 37 dB(A) or lower at the assessment position of the nearest noise sensitive premises. That calculation combines the unit's rating with distance, reflecting surfaces and the position of the neighbour's window. It is set out in heat pump noise and planning rules.

What to actually compare when you get quotes

  1. The design flow temperature the quote assumes, because it changes efficiency more than the brand does.
  2. The SCOP at that flow temperature, not the headline SCOP at 35C.
  3. The sizing basis, checked against the room by room heat loss calculation rather than the size of your old boiler.
  4. The MCS 020 (a) sound calculation result at the proposed position.
  5. The warranty terms and the availability of local service engineers for that brand, which matters more in year eight than in year one.

None of these units is a bad product, and the honest conclusion from the trial data is that the installation team's design decides your outcome far more than the badge does. That is why MCS certification and the survey get more space on this site than brand comparisons do.

Every county page on this site carries a local calculator and the current grant position, so start at our coverage map. The full heat pumps guide covers the rest of the system, and if you are weighing up solar panels alongside it, the combined electrical picture is worth planning in one pass.

Clearline does not sell, supply or endorse any product named here. Our MCS-certified, fully insured installation teams install and commission every system. Specifications are taken from manufacturer pages and datasheets except where marked review sourced, and were checked on the date shown.

FAQs

Comparison questions, answered

Which is the best air source heat pump in the UK?

There is no single answer, and the field data argues the question is less important than it looks. The Electrification of Heat trial found high variation in performance between installations of similar equipment, with a median in situ SPF of 2.80. Design quality, sizing and flow temperature move your bill further than the choice between these brands.

What is the difference between R290 and R32?

R290 is propane, quoted by Vaillant at a global warming potential of 3, and it enables the 70 to 75C flow temperatures that make radiator retrofits and immersion-free hot water viable. R32 remains in use across mainstream lines including the Daikin Altherma 3 R and the Ideal Logic Air. The practical difference for a homeowner is the maximum flow temperature available.

Why do SCOP figures vary so much between brands?

Mostly because they are measured at different flow temperatures. Ideal quotes 5.16 to 5.19 at 35C flow but 3.7 to 3.73 at 55C for the same units, and Samsung quotes up to 4.84 at 35C against 2.82 to 3.03 at 65C. Always check the condition attached to the number before comparing two brands.

Is the Octopus Cosy 6 a rebadged unit?

It is described as Octopus Energy's own-brand R290 monobloc, with a compact footprint of 855mm by 1125mm and a real world SCOP of up to 4.12 claimed in a review. Nominal output figures vary between sources, so confirm the current kW rating against the Octopus datasheet before relying on it.

Does Grant really make a 15.5 kW domestic unit?

Yes. The Aerona 290 range runs 4, 6.5, 9, 12 and 15.5 kW single phase, each rated at minus 5C air temperature and 55C water flow, and the 15.5 kW is sold through Octopus Energy for larger homes. Rating at minus 5C is a more demanding basis than many nominal figures, so compare like with like.

How do I compare noise figures between brands?

Carefully, because manufacturers publish sound power and sound pressure and the two are not interchangeable. Sound pressure figures also depend on the stated distance. For planning purposes the number that counts is the MCS 020 (a) calculation result at your neighbour's assessment position, which must be 37 dB(A) or lower.

Figures and specifications in this guide are sourced below and were checked on the date shown. Rates and product specifications change; we confirm the current picture on your free design call.

Sources
  • Vaillant, aroTHERM plus product and specification pages: outputs, R290 with GWP of 3, SCOP up to 5.03, 75C flow, minus 25C operation, sound pressure below 30 dB(A) at 3 metres vaillant.co.uk
  • Mitsubishi Electric Ecodan R290 datasheet (distributor copy): 5 to 16 kW outputs, 75C flow, minus 25C operation saturnsales.co.uk
  • Solarinfo and Heatable, Mitsubishi Ecodan reviews (secondary): SCOP 3.5 to 4.2 by size, sound power figures, Ultra Quiet PUZ variants solarinfo.uk
  • Daikin, Altherma 3 R product page and Altherma 3 H HT product page and technical brochure: R32 Bluevolution, A+++ label, minus 25C operation, 70C flow, SCOP 4.71 at 35C, 38 dB(A) and 35 dB(A) sound pressure at 3 metres daikin.co.uk
  • Samsung Climate Solutions, EHS Mono R290 and EHS Mono HT Quiet product pages: capacities, SCOP up to 4.84 at 35C, SCOP 2.82 to 3.03 at 65C, 35 dB(A) quiet modes samsung-climatesolutions.com
  • Grant UK, Aerona 290 range page and technical document rev 1.8, April 2026: outputs rated at minus 5C air and 55C flow, R290, A+++ label grantuk.com
  • Ideal Logic Air brochure and distributor listing, with review-sourced datasheet SCOP figures dwellow.co.uk
  • Worcester Bosch, Compress 7001i AW product page and technical data sheet: 5, 7, 9 and 13 kW outdoor units worcester-bosch.co.uk
  • Future Heat, Octopus Cosy 6 review (secondary): own-brand R290 monobloc, 855mm by 1125mm footprint, claimed real world SCOP up to 4.12 futureheatltd.co.uk
  • Energy Systems Catapult, Electrification of Heat performance data: median in situ SPF 2.80, variation between installations es.catapult.org.uk
  • MCS 020 (a), Air Source Heat Pump Sound Calculation for Permitted Development Installations, Issue 1.0, July 2025 mcscertified.com
Free, no obligation

Get my free quote

Takes about two minutes. We call or text within one working day to book your free 30-minute video design call at a time that suits you. We design it around your roof and your numbers, and our MCS-certified, fully insured installation teams install it.

Installations can only go ahead for homeowners, as the system is fixed to the property. Do carry on if you own it, or you are about to.
Flats and apartments usually share a roof, which rules most installations out. Send your details anyway and we will tell you honestly what is possible.
1 Where is your home?
Please add your full postcode
Please add your house number
2 About you
Please add your first name
Please add your last name
Please add a UK number
Please add a valid email
3 Your property
Do you own your home?
Please let us know
Property type
Please choose your property type
4 What are you after?
Please pick one, "not sure" is fine
Roughly is fine
Please choose a timeframe
5 When shall we call?
Best time for you (optional, but it helps)

We never call after 8pm.

We call or text within one working day to book your free 30-minute video design call. Free, no obligation. No home visit needed.

Your design call is with Niall or Vince, our residential energy consultants.

Call 07782 219224

By submitting you agree we can contact you about your enquiry. We never sell your details and never pass them to a panel of companies to ring you. See our privacy notice.